Air Quality for the National Bio and Agro-Defense Facility (NBAF)

CPP Wind > Portfolio > Air Quality for the National Bio and Agro-Defense Facility (NBAF)
nbaf-01

The National Bio and Agro-Defense Facility (NBAF), located in Manhattan, Kansas, will provide the United States with its first integrated facility for research, diagnostics, training, and evaluation (RDT&E) for agricultural and zoonotic diseases. Slated to be fully operational by 2022, NBAF will have the capability to address threats from high-consequence zoonotic disease agents and foreign animal disease (FAD) agents.

Early in the project, the Kansas Department of Health and Environment (KDHE) designated the NBAF a major pollutant source, which requires demonstration that emissions from the boilers, generators and incinerators will not cause or contribute to air pollution above the regulated thresholds. Specifically, the facility must meet the National Ambient Air Quality Standards (NAAQS) and Prevention of Significant Deterioration (PSD) increments for the following pollutants:

  • Particulate matter (PM10)
  • Sulfur dioxide (SO2)
  • Nitrogen dioxide (NO2)

CPP’s air quality team was chosen to conduct an Air Quality Impact Assessment (AQIA) as part of the permitting process. Having previously tested NBAF in the wind tunnel for potential health and odor impacts at the building air intakes, our team already understood the facility’s mission and requirements.

NBAF includes two laboratory facilities and three outbuildings. One of the outbuildings, the Central Utility Plant (CUP), features seven 800 BHP Scotch marine (fire-tube) boilers, which provide steam service to the main lab building. All boilers are equipped with dual fuel burners (natural gas and #2 fuel oil), and one of the seven boilers serves as a backup unit. The backup boiler is not required to meet design steam loads, and fuel oil is only used for emergency operation of the boilers. Otherwise, natural gas is the design fuel.

In addition, the CUP relies upon seven 2,000 kW diesel backup generators for emergencies. These are EPA Tier 2 certified engines available exclusively for emergency situations, maintenance and testing purposes. One of these seven generators serves as a redundant unit and is not required to meet design loads under emergency conditions.

Finally, two identical medical waste incinerators in the laboratories also exhaust to the atmosphere. Collectively, the boilers, the generators, and the incinerators represent 16 total emission sources that required investigation for air quality compliance.

To assess compliance with NAAQS and PSD increments, CPP conducted the AQIA using the EPA’s preferred modeling system, AERMOD. Our team evaluated air quality impacts from the boilers, generators, and incinerator exhausts, and our initial modeling efforts suggested that NAAQS compliance might be problematic in worst-case boiler operating scenarios. However, the facility passed with flying colors under more realistic boiler operating conditions. Considering alternate stack heights allowed the proposed facility to meet NAAQS and PSD increment requirements with minimal operational restrictions.

Boilers
  • No more than 6 boilers may operate at the same time.
  • The primary fuel is natural gas.
  • The emergency fuel is ultra-low sulfur diesel (ULSD), having an SO2 content of 15 parts per million (ppm) or fewer.
  • Low NOx burners are to be rated at 30 ppm or lower.
  • Particulate emissions are limited, and record keeping and reporting are required.
Generators
  • Maintenance and readiness testing of the generators is limited to 100 hours per year and may only take place between 6:00 AM and 6:00 PM.
  • The fuel for the generators is also ULSD.
  • No operational restrictions apply during emergency situations, and record keeping and reporting are required.Based upon the results of CPP’s earlier wind tunnel study and our evaluation of these AERMOD exhaust dispersion results, the Kansas Department of Health and Environment issued an operating permit, and the NBAF project was able to move forward as planned. All of us at CPP are pleased to have played a role in protecting our country’s security and ensuring biohazard emergency readiness.

Project Team

CPP Project Director:
Dr. Ron Petersen
info@cppwind.com

Project Manager:
Timothy Barr

Project Technical Director:
Eugene Cole
Department of Homeland Security Science and Technology Directorate

Architect:
NBAF Design Partnership (NDP)
Includes the following firms:
Perkins + Will www.perkinswill.com
Flad Architects www.flad.com
Merrick and Company www.merrick.com
Ccrd Engineers www.ccrd.com
Affiliated Engineers Inc. www.aeieng.com/index.php/home

Project Details

Client name:
The National Bio and Agro-Defense Facility
Location:
Manhattan, Kansas
Architect:
NBAF Design Partnership (NDP)